    Nor-Lake Walk-In Cooler Condensing Unit Replacement in San Jose

    The walk-in at a sushi restaurant was warming up because the compressor had shorted out. We replaced the condensing unit, the evaporator coil and the defrost timer, then charged and started the system.

    Repair at a glance

    CitySan Jose, CA
    ApplianceWalk-In Cooler
    CategoryCommercial
    Brand & modelNor-Lake RRT64C1E-IAA-959
    Repair date
    Customer complaintThe walk-in cooler temperature was too high.
    DiagnosisThe compressor had a short circuit and no longer worked. The condensing unit assembly needed to be replaced.
    Repair cost$3,701
    Warranty6 months on parts and labor
    OutcomeRepaired

    What the customer told us

    The restaurant called because the temperature in their Nor-Lake walk-in cooler was climbing too high.

    What we found

    We opened the condensing unit on top of the box. The compressor had a short circuit in the windings and would not run, so the box had no cooling at all. The old unit had a Copeland compressor, and the coil and base showed years of dirt and corrosion.

    How we repaired it

    We offered two options: a compressor only, or a complete condensing unit. The customer chose the full assembly. We recovered the system, removed the old condensing unit, set the new 6,760 BTU unit (RRT64C1E-IAA-959) on the roof of the box and brazed in the suction and liquid lines. The evaporator coil inside the box was replaced as well, along with the defrost timer.

    Testing

    After a pressure test and vacuum we charged the system and started it up. We checked pressures, the fan motors and the defrost timer, and watched the box temperature come down.

    Photos from this repair

    • Nor-Lake RRT64C1E-IAA-959: Kitchen of the restaurant with the walk-in cooler
      Kitchen of the restaurant with the walk-in cooler.
    • Nor-Lake RRT64C1E-IAA-959: Nor-Lake walk-in cooler panel
      Nor-Lake walk-in cooler panel.
    • Nor-Lake RRT64C1E-IAA-959: Old condensing unit with the housing open
      Old condensing unit with the housing open.
    • Nor-Lake RRT64C1E-IAA-959: Old condenser coil
      Old condenser coil.
    • Nor-Lake RRT64C1E-IAA-959: Shorted compressor in the old condensing unit
      Shorted compressor in the old condensing unit.
    • Nor-Lake RRT64C1E-IAA-959: Old condensing unit on top of the walk-in
      Old condensing unit on top of the walk-in.
    • Nor-Lake RRT64C1E-IAA-959: Condensing unit area during the replacement
      Condensing unit area during the replacement.
    • Nor-Lake RRT64C1E-IAA-959: Condenser and drier during the swap
      Condenser and drier during the swap.
    • Nor-Lake RRT64C1E-IAA-959: Liquid line drier on the new unit
      Liquid line drier on the new unit.
    • Nor-Lake RRT64C1E-IAA-959: Empty base after the old unit was removed
      Empty base after the old unit was removed.
    • Nor-Lake RRT64C1E-IAA-959: New condensing unit set in place
      New condensing unit set in place.
    • Nor-Lake RRT64C1E-IAA-959: New unit with gauges connected
      New unit with gauges connected.
    • Nor-Lake RRT64C1E-IAA-959: New condensing unit connected on top of the box
      New condensing unit connected on top of the box.
    • Nor-Lake RRT64C1E-IAA-959: New unit after the lines were brazed
      New unit after the lines were brazed.
    • Nor-Lake RRT64C1E-IAA-959: Compressor and lines on the new condensing unit
      Compressor and lines on the new condensing unit.
    • Nor-Lake RRT64C1E-IAA-959: Finished installation on top of the walk-in cooler
      Finished installation on top of the walk-in cooler.